GKS-550 ( 500kVA )

Watch video

Features and benefits

  • Maximum 550kVA standby power at 230/400v @50Hz 1500rpm
  • High quality and reliable eight-cylinder 15.6l Scania turbo diesel engine
  • Ideal for business applications
  • Silent canopy which can stand outside with lockable doors
  • Automatic changeover (ATS), maintenance free batteries and trickle charger included
  • H-specification insulation, brushless alternator with AVR provides stable output
  • Four-way protection system included
  • Easy to use digital controller with auto and manual start options
  • All sets undergo a comprehensive testing/pre delivery inspection prior to delivery
  • Peace of mind of earlier of one year/1000 hour warranty

Engine

  • Scania heavy-duty diesel engine
  • Eight cylinder equipped with wet cylinder liners
  • Engine management system
  • Replaceable wet type cylinder liners
  • 24v DC starter and charge alternator
  • Replaceable fuel filter, oil filter and dry element air filter
  • Cooling radiator and fan
  • Fuel connection hoses and manual sump oil drain valve
  • Exhaust silencer
  • Maintenance free battery including rack and cables
  • Jacket water heater (as option)
  • Scania engine manual

Alternator

  • Brushless, single bearing system, four poles
  • Insulation class H with circuit breaker protection
  • Standard degree of protection IP21
  • Self-exciting and self-regulating
  • AVR SX440 included
  • Screen protected and drip proof
  • Stator winding with 2/3 pitch for improved harmonics
  • Close voltage regulation

Chassis

  • Steel chassis and anti-vibration pads
  • Base frame design incorporates an integral fuel tank
  • The generator can be lifted or carefully pushed/pulled by the base frame
  • Includes diesel level sensor information to the controller

Canopy

  • Ventilation parts are designed with modular principles
  • Weather resistant and lined with sound reducing foam
  • All metal canopy parts are painted by powder paint
  • Panel window
  • Lockable doors on each side
  • Easy maintenance and operation
  • Easy lifting and moving
  • Insulated engine exhaust system
  • Exterior emergency stop push button
  • General specifications

  • Structure type
  • Dimensions Length x Width x Height
  • Dry weight
  • ATS unit included
  • Four-way protection system included
  • GKS-550

  • 550-KVA

  • Silent weather resistant enclosure
  • 4200mm x 1500mm x 2050mm
  • 5500kg
  • Engine specifications

  • Engine make
  • Diesel generator model
  • Displacement
  • Cylinder bore/stroke
  • Fuel system
  • Cylinders
  • Cylinder arrangement
  • Engine output power
  • Turbocharged or normally aspirated
  • Cycle
  • Combustion system
  • Compression ratio
  • Fuel tank capacity
  • Fuel consumption 100%
  • Fuel consumption 75%
  • Fuel consumption 50%
  • Fuel consumption 25%
  • Oil type
  • Oil capacity
  • Cooling method
  • Coolant capacity (including radiator)
  • Starter
  • Governor system
  • Engine speed
  • GKS-550

  • 550kVA

  • Scania
  • DC16 43A-Ref 10-24
  • 15.6l
  • 127mm x 154mm
  • Scania EMS governor
  • 8
  • V-block
  • 439kW
  • Turbocharged
  • Four stroke
  • Electronic unit injectors
  • 18:1
  • 810l
  • 100.34 l/h
  • 73.69 l/h
  • 50.17 l/h
  • 25.09 l/h
  • 15W40
  • 35l
  • Radiator water-cooled
  • 70l
  • 24v DC
  • Electronic
  • 1500rpm
  • Alternator specifications

  • Alternator brand
  • Standby power output
  • Prime power output
  • Insulation class
  • Type
  • Phase and connection
  • AVR
  • AVR model
  • Voltage regulation
  • Voltage
  • Rated Frequency
  • Voltage regulate change
  • Phase change rate
  • Power factor
  • Protection class
  • Stator
  • Rotor
  • GKS-550

  • 550-KVA

  • Stromer
  • 550kVA
  • 500kVA
  • H
  • Brushless
  • Three phase, Four wire
  • SX440
  • ± 1%
  • 230/400v
  • 50Hz
  • ≤ ±10% UN
  • ± 1%
  • 0.8
  • IP21
  • 2/3 pitch
  • Single bearing

Control system

Control supervision and protection panel is mounted on the genset base frame. The control panel is equipped as follows:

Auto mains failure control panel

  • Smartgen series automatic transfer switch module
  • HGM7220 electronic controller
  • Emergency stop push button
  • Static battery charger
  • Four-pole electrically and mechanically interlocked ATS

Generating set control module HGM7220 features

  • This module is used to monitor a mains supply and automatically start a standby generating set
  • Event logging and shutdown alarms
  • STOP/RESET-MANUAL-AUTO-TEST-START

Metering via LCD display

  • Generator volts (L-L/L-N); mains volts (L-L/L-N)
  • Generator amps (L1, L2, L3); generator (kVA and kW)
  • Generator frequency (cos)
  • Engine hours run; plant battery volts
  • Engine oil pressure (psi and bar)
  • Engine speed (rpm)
  • GSM SMS signal
  • Engine temperature (degrees C)

Automatic shutdown and fault conditions

  • Under/over speed; fail to start
  • High engine temperature; fail to stop
  • Low oil pressure; charge fail
  • Under/over generator volts; over current
  • Under/over generator frequency; emergency stop
  • Under/over mains frequency
  • Under/over mains voltage

*All ratings are quoted at maximum ratings at sea level and derating will be applicable for altitude and power factor